How to convert GOT900 series screen data to GOT1000 series screen data

How to convert GOT900 series screen data to GOT1000 series screen data
Mitsubishi Electric Automation (Shanghai) Co., Ltd.
------ Applies to GT Designer2 Version2.33K Chinese

one. Steps for converting GOT-F900 series screen data to GOT1000 series screen data
1. For GOT-F900 series screen data created with GT Designer / GT Designer2 software:
1 Use the GT Designer2 Version2 software to open the screen data of the GOT-F900 series previously created with the GT Designer/GT Designer2 software.
2 Then select the "Common Settings" menu / "System Environment", in the "System Environment" dialog box, change the "GOT type" from GOT-F900 to GOT1000.

2. For GOT-F900 series screen data created with FX-PCS-DU/WIN-C software:
1 Create a new GT11**-VC or GT11**-QC project using GT Designer2 Version2 software.
2 Then select “Project” menu/“Read other project...” and a dialog like the one shown below will pop up.

3 Click the “Reference” button in the dialog box shown above to open the GOT-F900 series screen data (*.dup) created with the FX-PCS-DU/WIN-C software, and then check the source to be read in. Picture data and click on the "Execute" button.

Note: After importing data by the above method, some functions in the original DU/WIN screen data and some functions not supported by the GOT1000 series may be lost. Therefore, be sure to check the original data after importing the data.

two. To convert GOT-A900 series screen data to GOT1000 series screen data
1 Use the GT Designer2 Version2 software to open the screen data of the GOT-A900 series created with the GT Designer/GT Designer2 software.
2 Then select the "Common Settings" menu / "System Environment". In the "System Environment" dialog box, change "GOT Type" from GOT-A900 to GOT1000.

Explanation: When using the GT Designer2 Version2 software to open the GOT900 series screen data created with the GT Designer software, select "File Type" as the "GT Designer File (A9GOTP.GOT)" in the "Open" dialog box.

Note: It is not possible to convert GOT1000 series screen data to GOT900 series screen data.